COOLING
TOWER
Fan
type cooling towers are installed at Patratu Thermal Power Station. The purpose
of cooling tower is to cool the circulating water, which is heated in
condensers by exhaust steam of turbines.
One
cooling tower (from 1-4) is designed for unit rate of 50MW capacity and cooling
tower number 5 and 6 are designed for 100MW capacity units.
Cooling towers are equipped with fans of induced type,
designated for operation under conditions of tropical climate. Fans give air
steam by means of which the circulating water is cooed. For better contact of
air with water and for more effective heat transfer, water coming from
condensers of steam turbine is distributed uniformly in cross-section of
cooling tower, sprayed by means of special devices and flows down to basin in
separate small jets.
Between
fan and level of water of supply water of supply water to be cooled, there are
wooden nets, which change the direction of air steam and considerable carryover
of water drops by air steam. Evaporation of water in cooling tower is about 2%
of the water flow of closed circulating system condenser cooling tower. Carry
over of water from cooling tower is approximately equal to 1% of the water flow
of the above system.
Area of spraying of one cooling tower- 1200 sq. mts.
Capacity of one cooling tower- 7730 cu.mts./hr.
Temperature drop- 9.80C
Density of spraying- 6.45M/V
Cooling
tower having density of spraying 6.45M/V and outside air temperature 32.20C
measured by wt thermometer provides cooling of water up to a temperature of
36.50C.
If the
flow of water through condenser is equal to 800 cu. Mt./hr. and water
temperature is 36.50C, the turbine may operate with rated power if
parameters of steam are not less than the rated ones.
Cooling tower consists of six right angled
sections with size of 12m. X 18m. in axis and square of 200m. each.
Cooling tower includes underground part consisting of
water basin and overhead part consists of frame, fencing, structure, sprayer,
with water distribution devices and ventilation fan installation. Water basin
is common for all the six sections and is made of monolithic reinforced concrete.
At the place of water, branching from basing to gravity channel, there is a
well with two rowed grooves for installation of cleaning screens. For discharge
and overflow, the basin is equipped with pipelines, which are connected to the
mains of industrial storm water sewerage. Water supply to each section is
effected from common distribution header through separate pipes with shut-off
gate valves, which enable to stop any of the sections of cooling tower for
inspection or repair. Exhaust fans are located in the center of each section.
Outside casing of cooling tower and sparing device are made of separate sheets
of corrugated asbestos sheet.
Comments