Abstract:
In this paper we have dealt with the high voltages testing techniques and High voltage measurement techniques.Different techniques like Chubb-Fortescue Method and Peak value measurement are also explained in detail.
The method of measurement of voltage with the help of Sphere Gap and Construction of Sphere Gap and its Effects of earthed objects and atmospheric conditions on the accuracy of measurement
are explained in details.Other techniques like Principle of measurement of voltage by Electrostatic Voltmeters and its Construction of Electrostatic Voltmetres help in study of High Voltages.
Principle of Potential Dividers And types of potential dividers circuit are also covered in this paper.
High test voltages generated in laboratories require special techniques for their measurement. Each type of high voltage namely; ac (), dc (=) and impulse () can be suitably measured with more than one different techniques. The choice of the method of measurement in a laboratory is a matter of convenience, cost and the accuracy required for the measurement besides the safety. The complications in measurements increase with the magnitude of the voltage desired to be measured. The problems confine mainly with respect to the large structures of the device and the electric stress control techniques applied to prevent PB and flash overs.
The high voltage measurement techniques in electric power systems are different. These are not discussed in this course.
Different measurement techniques adopted for the three different types of voltages are given in Table 30.1
As it can be seen in this table, the earliest technique of sphere gap and the modern and most accurate technique of potential divider are applicable for the measurement of all the three types of voltages and both their polarities. The sphere gap technique, used widely for over a century, is not used any more. The disadvantages of this method are many. It does not provide a continuous measurement of the voltage and a flashover between the two spheres is essential. This measurement technique is not an accurate one. It may give error upto 3% in the measurement.
The electrostatic voltmeter, suitable for the measurement of ac (rms) and dc voltages, is one of the most accurate instrument. However, due to its size, cost and adjustment problems, it is not used very widely. For the measurement of ac power frequency voltage, the simplest way is to measure the voltage on the primary side or at the low voltage side of the ac test transformer and calibrate the dial of the low voltage voltmeter by multiplication of the turns ratio to get the high output voltage. However, this technique could give rise error in two ways. First, in case of high capacitive loads, the leading current output from the test transformer results in higher actual voltage output than measured with the help of trunks ratio at the primary side, the well known Ferranti
effect as shown in Fig. 30.1. Secondly, if the output voltage in not perfectly sinusoidal, the peak value is not times the rms value. To overcome this problem, measurement of peak value of the output voltage at the high voltage side is recommended.
Global Breakdown or rupture of insulation properties of dielectrics in general take place at the peak of the voltage applied. The power frequency ac voltage may not always have perfect sinusoidal waveform, the dc output voltage may have ripple and for the impulse voltage the peak is significant. Hence, the measurement of peak magnitude of these voltages is therefore of great importance.
Chubb-Fortescue Method
The most simple yet accurate method for the measurement of peak values of ac power frequency voltage was proposed by Chubb and Fortescue in 1913. The circuit diagram for this method is shown
The measuring instrument in this circuit, an ammeter, reads the magnitude of charge per cycle or the mean value of the current
hence,
the limits of integration are shown in Figure
If both, the +ve and -ve, peak values are equal, the expression for the charging current of the HV capacitor can be written as,
(30.2)
With knowledge of exact value of f and C, the value of dc current measured gives 2Umax , the actual peak to peak value of the ac voltage.
Peak value measurement
A number of rectifier circuits have been proposed for the measurement of peak value of ac power frequency and impulse voltages to work with capacitive voltage dividers. The first circuit of its kind was proposed by Davis, Bowdler and Strandring in 1930, shown in Fig 30.4
In this circuit, the measuring capacitors Cm is charged to the peak value , the lower arm voltage of the capacitive voltage divider. If U2 is decreased, Cm will hold the charge and the voltage across it will not change. Because of the reverse bias current of the diode, there is a danger that
U2 will gain negative dc component over the time. Hence Um will no longer follow the change in U2 . Therefore, discharge resistors R2 and Rd must be included in this circuit. The time constant RdCm should be between 0.5 - 1 sec to obtain a good response. When the circuit response conditions are taken care, the peak value of the voltage to be measured is given by the relation
Sphere Gap
This is one of the oldest technique adopted for the measurement of all the types (dc =, ac ~ and impulse ) high voltages of either polarity. It remained the most widely used method for decades. The field between two identical spheres is a classical example of "weakly nonuniform" field. The breakdown characterstic of such a gap is linear for the gap distances not greater than the radius of the spheres. Measurement voltage is made as a function of minimum distance at which it can flash over or sparkover.
The breakdown voltage of the gap does not depend upon the duration of application of voltage and also not upon its variation with time.
Construction of the Sphere Gap
A sphere gap consists of two adjacent metal spheres of equal diameters whose separation gap distance is variable. The ability to respond to peak values of impulse voltages, if the time to peak is not too short ( 1-3 μsec), is governed by a short statistical time lag or the delay in time required for the availabiilty of an electron to initiate an electron avalanche and hence the breakdown.
Vertical sphere gap. 1. Insulating support. 2. Sphere shank. 3. Opening gear, showing maximum dimensions. 4. High-voltage connection with series resistor. 5. Stress distributor, showing maximum dimensions. P. Sparking point of .v. sphere. A. Height of P above ground plane. B. Radius of space free from external structures. X. Item 4 not to pass throuhg this plane within a distance B from P. Note: This figure is drwan to scale for a 100-cm sphere for gap spacing equal to their radius.
1. Within the limited gap distance between the spheres, a weakly nonuniform field exists, hence no PB or corona appear before the complete breakdown or flashover.
2. For a given dimension of the diameter/radius of the spheres and a gap distance between them, the magnitude of the voltage at which the breakdown occured is read from the standard calibrated tables available for different types of voltages and for both their polarities.
3. The inaccuracy of measurement of voltage by this method is about 3%.
4. The accuracy to measurement of voltage with sphere gap is considerably affected by earthed objects around the gap since they form stray capacitance.
Correction Factor
Since in general the actual air density during measurements differ from the reference conditions, the breakdown voltage of the air gap is given as
Ub = kd Ub0
where Ub0 corresponds to the table values and kd is a correction factor related to air density.
The actual relative air density (RAD) is given in general terms by
where
p0 = air pressure for standard conditions
p = air pressure at the test conditions
t0 = 20 0C
t = temperature in 0C at the test conditions.
The correction factor kd, given in table below for increasing values of RAD are slightly non linearly. However, it can be seen from the table that the correction factor kd is almost equal to RAD,δ.
Air density correction factor
Relative air density RAD, δ
Correction factor kd
0.70
0.72
0.75
0.77
0.80
0.82
0.85
0.86
0.90
0.91
0.95
0.95
1.00
1.00
1.05
1.05
1.10
1.09
1.15
1.13
Disadvantages:
For the measurement, breakdown in the gap has to take place.
Continuous measurement of the voltage is not possible.
This method is not very accurate.
Electrostatic Voltmeters produced upto 1000 kV rated voltage are suitable for the measurement of ac power frequency and also for higher frequency rms voltages. They can also measure dc voltages.
For higher voltage range compact voltmeters with SF6 gas or vaccum insulation gap are also produced.
These voltmeters were suggested by Kelvin in 1884 for the measurement of rms value of power frequency voltage. They are developed to follow the Coulomb's law which defines the static electric field as a field of force.
The field produced between two parallel plate electrodes with shaped profile brims, is a uniform field.
If the voltage applied across these parallel plates having a gap distance 'd' is U, then the uniform field produced in the gap between
them will have an intensity E equal to U/d.
The attracting force F between the plates on area A of the electrodes is equal to the rate of change of stored electrical energy Wel per unit distance in the capacitance formed between the plates.
Therefore
Where = permittivity of the insulating medium d = gap distance between the parallel plate electrodes of area A.
The attracting force is always positive independent of the polarity of the voltage. If the voltage is not constant, the force is also time (frequency) dependent. Then the mean value of the force is used to measure the rms value of the voltage. Thus
where T is a proper integration time.
Electrostatic voltmeters are arranged such that one of the electrodes or a part of it is allowed to move.
Thus electrostatic voltmeters are rms indicating instruments if the force integration and its display follows eqn-32.2.
Various voltmeters developed differ in their use of different methods of restoring forces required to balance the electrostatic attraction. This can be achieved by suspension of the moving electrode on one arm of a balance or its suspension on a spring or the use of a pendulous or torsional suspension.
The small movement is generally transmitted and amplified by a spot light and mirror system, but many other systems have also been used.
The electrostatic measuring device can be used for absolute voltage measurements since the calibration can be made in terms of the fundamental quantities of the gap length and forces.
For a constant electrode separation 'd' the integrated forces increase with (Urms)2 and thus the sensitivity of the system for low ranges of the rated voltages of the instrument is small. This disadvantage is
overcome, however by varying the gap length in appropriate steps.
The high pressure gas or even high vacuum between the electrodes provide very high resistivity, therefore the low active power loss.
The measurement of voltages lower than about 50V is , however not possible as the forces become too small.
The load inductance and the electrode system capacitance, however, form a series resonant circuit which must be damped, thus limiting the frequency range.
Sectional view of a 1000 kV standard electrostatic voltmeter using SF6 gas is shown below in Fig. 32.2
A five section capacitor and oil insulated bushing is used to bring the extremely high voltage into the instrument metal tank, filled with pressurized SF6
The HV electrode and earthed plane provide uniform electric fields in the region of the 5 cm diameter disc set in a 65 cm diameter guard plane.
The measurement accuracy of this instrument is of the order of 0.1%.
Principle of Potential Dividers :For the measurement of High Voltages of any type, the best technique is by dividing the voltage. The HV potential divider arms could be pure capacitive, pure resistive or a combination of the two. The essential requirement is that the wave shape to be measured is correctly reproduced on the oscillograph with a known voltage reduction ratio. The general potential divider technique is shown in the following Figure 33.1.
Z1 - the high voltage arm of the divider. It could be pure C, pure R or combination of R and C as per requirement.
Values of Z1 and Z2 are chosen such that the potential across Z2 is around 100 V
The voltage division ratio can be given as; For the circuit in Fig 33.1 where Z"2 = terminal impedence of oscilloscope
For the measurement of high test voltages the technique of potential dividers is most accurate. It provides a continuous measurement of all the types of applied high voltages i.e. dc, ac and impulse. However, the suitability of the type of divider depends upon not only the type of voltage but also upon the range of magnitude of the voltage to be measured.
The types of potential dividers or basically the construction of the HV arm and their suitability are described in the following:
1. Pure Capacitance Voltage Dividers:
The HV arm of the capacitive voltage dividers, usually having their capacitance in pF range, are compressed gas or vacuum capacitors. The nF range HV capacitors are built in stack or in series a number of capacitors made out of polypropylene or paper filled with oil. In the absence of stray capacitances to earth with such HV capacitors, these provide desired exact value of low capacitance and small dimensions of the HV capacitive arm. The value of low voltage arm of the divider is normally chosen in μF range. Compressed gas (SF6) filled HV capacitors are built even above 1000 kV (rms) rating. These can also be used as standard capacitors. In Fig 33.2, a photograph and a sketch of such a capacitor are shown. The value of inductance of the long lead (in mts) connecting the low voltage electrode inside such a capacitor causes problems in giving a good response of the divider. Necessary constructional precautions are therefore taken in their design.
Pure capacitance voltage dividers are suitable for the measurement of power frequency and impulse high voltages. However, the cost of the HV capacitors is high and their cost and size increases with their voltage rating.
2. Pure Resistance Potential Dividers
The high potential drop across a resistive arm by simple Ohm's law is used to reduce the voltage to a measurable quantities, circuits for such measurement are shown in Fig 33.3 (a) and (b)
Such pure resistive arm or divider can be used for the measurement of dc, ac as well as impulse voltages. The wave forms of ac and impulse voltages could also be recorded with the help of an oscilloscope. However, while measuring very high voltages, the resistive arm inductance and stray capacitance cause large error in the accuracy of measurement and hence in response of the measuring device.
The wire-wound resistors used earlier were made of constantan, Cu & Ni, manganin, cu, Mn, Ni or Gr and also of nichrome. To overcome the error caused due to inductance of the wire wound resistors, thin film resistors are now used. A conducting element thin film is deposited on the surface of a glass or ceramic rod or tube. The value of the desired resistance is obtained by varying the thickness of the thin film. Such films could be of carbon, metal oxide; stannic and antimony oxides. Nickel-Chromium thin film is obtained by their evaporation in vacuum. Resistive voltage dividers are produced both
screened (also known as shielded) and unscreened. Since the effect of stray capacitance is not uniform, it causes a non-uniform potential gradient along its length.
3. Mixed Resistive and Capacitive Dividers
The problem caused by the stray capacitance in resistive voltage divider is over come by placing actual capacitors in parallel with the resistor units of the HV arm. This gives rise to a mixed resistive and capacitive divider used for highest voltage range of impulse voltage measurement. These are also known as 'damped capacitive divider' or RC divider. These were first introduced by Elsner in 1939, [6.1 ] . The simplified equivalent circuit of such a divider is shown in Fig 33.4
In this Figure R' represents the resistance of single element of the HV arm where a number of them are in series. C'p represents the capacitance across each of such element and C'e, is the stray capacitance to earth of the element.
References:
1. http://nptel.ac.in/courses/Webcourse-contents/IIT-KANPUR/HighVoltageEngg/ui/Course_home6_30.htm
2. http://www.springer.com/cda/content/document/cda_downloaddocument/9783642453519-c2.pdf?SGWID=0-0-45-1443916-p176426054 3. Arrillaga, Jos; High Voltage Direct Current Transmission, second edition, Institution of Electrical Engineers, ISBN 0 85296 941 4, 1998. 4. Narain G. Hingorani in IEEE Spectrum magazine, 1996. 5. ABB HVDC website. 6. ABB HVDC website. 7. Jos Arrillaga; Yonghe H. Liu; Neville R. Watson; Nicholas J. Murray (9 October 2009). Self-Commutating Converters for High Power Applications. John Wiley and Sons. ISBN 978-0-470-74682-0. Retrieved 9 April 2011. 8. Donald Beaty et al, "Standard Handbook for Electrical Engineers 11th Ed.", McGraw Hill, 1978 9. ACW's Insulator Info – Book Reference Info – History of Electrical Systems and Cables 10. R. M. Black The History of Electric Wires and Cables, Peter Perigrinus, London 1983 ISBN 0-86341-001-4 pages 94–96 11. Alfred Still, Overhead Electric Power Transmission, McGraw Hill, 1913 page 145, available from the Internet Archive 12. "Shaping the Tools of Competitive Power" 13. Thomas P. Hughes, Networks of Power 14. Rissik, H., Mercury-Arc Current Converters, Pitman. 1941, chapter IX.
In this paper we have dealt with the high voltages testing techniques and High voltage measurement techniques.Different techniques like Chubb-Fortescue Method and Peak value measurement are also explained in detail.
The method of measurement of voltage with the help of Sphere Gap and Construction of Sphere Gap and its Effects of earthed objects and atmospheric conditions on the accuracy of measurement
are explained in details.Other techniques like Principle of measurement of voltage by Electrostatic Voltmeters and its Construction of Electrostatic Voltmetres help in study of High Voltages.
Principle of Potential Dividers And types of potential dividers circuit are also covered in this paper.
High test voltages generated in laboratories require special techniques for their measurement. Each type of high voltage namely; ac (), dc (=) and impulse () can be suitably measured with more than one different techniques. The choice of the method of measurement in a laboratory is a matter of convenience, cost and the accuracy required for the measurement besides the safety. The complications in measurements increase with the magnitude of the voltage desired to be measured. The problems confine mainly with respect to the large structures of the device and the electric stress control techniques applied to prevent PB and flash overs.
The high voltage measurement techniques in electric power systems are different. These are not discussed in this course.
Different measurement techniques adopted for the three different types of voltages are given in Table 30.1
As it can be seen in this table, the earliest technique of sphere gap and the modern and most accurate technique of potential divider are applicable for the measurement of all the three types of voltages and both their polarities. The sphere gap technique, used widely for over a century, is not used any more. The disadvantages of this method are many. It does not provide a continuous measurement of the voltage and a flashover between the two spheres is essential. This measurement technique is not an accurate one. It may give error upto 3% in the measurement.
The electrostatic voltmeter, suitable for the measurement of ac (rms) and dc voltages, is one of the most accurate instrument. However, due to its size, cost and adjustment problems, it is not used very widely. For the measurement of ac power frequency voltage, the simplest way is to measure the voltage on the primary side or at the low voltage side of the ac test transformer and calibrate the dial of the low voltage voltmeter by multiplication of the turns ratio to get the high output voltage. However, this technique could give rise error in two ways. First, in case of high capacitive loads, the leading current output from the test transformer results in higher actual voltage output than measured with the help of trunks ratio at the primary side, the well known Ferranti
effect as shown in Fig. 30.1. Secondly, if the output voltage in not perfectly sinusoidal, the peak value is not times the rms value. To overcome this problem, measurement of peak value of the output voltage at the high voltage side is recommended.
Global Breakdown or rupture of insulation properties of dielectrics in general take place at the peak of the voltage applied. The power frequency ac voltage may not always have perfect sinusoidal waveform, the dc output voltage may have ripple and for the impulse voltage the peak is significant. Hence, the measurement of peak magnitude of these voltages is therefore of great importance.
Chubb-Fortescue Method
The most simple yet accurate method for the measurement of peak values of ac power frequency voltage was proposed by Chubb and Fortescue in 1913. The circuit diagram for this method is shown
The measuring instrument in this circuit, an ammeter, reads the magnitude of charge per cycle or the mean value of the current
hence,
the limits of integration are shown in Figure
If both, the +ve and -ve, peak values are equal, the expression for the charging current of the HV capacitor can be written as,
(30.2)
With knowledge of exact value of f and C, the value of dc current measured gives 2Umax , the actual peak to peak value of the ac voltage.
Peak value measurement
A number of rectifier circuits have been proposed for the measurement of peak value of ac power frequency and impulse voltages to work with capacitive voltage dividers. The first circuit of its kind was proposed by Davis, Bowdler and Strandring in 1930, shown in Fig 30.4
In this circuit, the measuring capacitors Cm is charged to the peak value , the lower arm voltage of the capacitive voltage divider. If U2 is decreased, Cm will hold the charge and the voltage across it will not change. Because of the reverse bias current of the diode, there is a danger that
U2 will gain negative dc component over the time. Hence Um will no longer follow the change in U2 . Therefore, discharge resistors R2 and Rd must be included in this circuit. The time constant RdCm should be between 0.5 - 1 sec to obtain a good response. When the circuit response conditions are taken care, the peak value of the voltage to be measured is given by the relation
Sphere Gap
This is one of the oldest technique adopted for the measurement of all the types (dc =, ac ~ and impulse ) high voltages of either polarity. It remained the most widely used method for decades. The field between two identical spheres is a classical example of "weakly nonuniform" field. The breakdown characterstic of such a gap is linear for the gap distances not greater than the radius of the spheres. Measurement voltage is made as a function of minimum distance at which it can flash over or sparkover.
The breakdown voltage of the gap does not depend upon the duration of application of voltage and also not upon its variation with time.
Construction of the Sphere Gap
A sphere gap consists of two adjacent metal spheres of equal diameters whose separation gap distance is variable. The ability to respond to peak values of impulse voltages, if the time to peak is not too short ( 1-3 μsec), is governed by a short statistical time lag or the delay in time required for the availabiilty of an electron to initiate an electron avalanche and hence the breakdown.
Vertical sphere gap. 1. Insulating support. 2. Sphere shank. 3. Opening gear, showing maximum dimensions. 4. High-voltage connection with series resistor. 5. Stress distributor, showing maximum dimensions. P. Sparking point of .v. sphere. A. Height of P above ground plane. B. Radius of space free from external structures. X. Item 4 not to pass throuhg this plane within a distance B from P. Note: This figure is drwan to scale for a 100-cm sphere for gap spacing equal to their radius.
1. Within the limited gap distance between the spheres, a weakly nonuniform field exists, hence no PB or corona appear before the complete breakdown or flashover.
2. For a given dimension of the diameter/radius of the spheres and a gap distance between them, the magnitude of the voltage at which the breakdown occured is read from the standard calibrated tables available for different types of voltages and for both their polarities.
3. The inaccuracy of measurement of voltage by this method is about 3%.
4. The accuracy to measurement of voltage with sphere gap is considerably affected by earthed objects around the gap since they form stray capacitance.
Correction Factor
Since in general the actual air density during measurements differ from the reference conditions, the breakdown voltage of the air gap is given as
Ub = kd Ub0
where Ub0 corresponds to the table values and kd is a correction factor related to air density.
The actual relative air density (RAD) is given in general terms by
where
p0 = air pressure for standard conditions
p = air pressure at the test conditions
t0 = 20 0C
t = temperature in 0C at the test conditions.
The correction factor kd, given in table below for increasing values of RAD are slightly non linearly. However, it can be seen from the table that the correction factor kd is almost equal to RAD,δ.
Air density correction factor
Relative air density RAD, δ
Correction factor kd
0.70
0.72
0.75
0.77
0.80
0.82
0.85
0.86
0.90
0.91
0.95
0.95
1.00
1.00
1.05
1.05
1.10
1.09
1.15
1.13
Disadvantages:
For the measurement, breakdown in the gap has to take place.
Continuous measurement of the voltage is not possible.
This method is not very accurate.
Electrostatic Voltmeters produced upto 1000 kV rated voltage are suitable for the measurement of ac power frequency and also for higher frequency rms voltages. They can also measure dc voltages.
For higher voltage range compact voltmeters with SF6 gas or vaccum insulation gap are also produced.
These voltmeters were suggested by Kelvin in 1884 for the measurement of rms value of power frequency voltage. They are developed to follow the Coulomb's law which defines the static electric field as a field of force.
The field produced between two parallel plate electrodes with shaped profile brims, is a uniform field.
If the voltage applied across these parallel plates having a gap distance 'd' is U, then the uniform field produced in the gap between
them will have an intensity E equal to U/d.
The attracting force F between the plates on area A of the electrodes is equal to the rate of change of stored electrical energy Wel per unit distance in the capacitance formed between the plates.
Therefore
Where = permittivity of the insulating medium d = gap distance between the parallel plate electrodes of area A.
The attracting force is always positive independent of the polarity of the voltage. If the voltage is not constant, the force is also time (frequency) dependent. Then the mean value of the force is used to measure the rms value of the voltage. Thus
where T is a proper integration time.
Electrostatic voltmeters are arranged such that one of the electrodes or a part of it is allowed to move.
Thus electrostatic voltmeters are rms indicating instruments if the force integration and its display follows eqn-32.2.
Various voltmeters developed differ in their use of different methods of restoring forces required to balance the electrostatic attraction. This can be achieved by suspension of the moving electrode on one arm of a balance or its suspension on a spring or the use of a pendulous or torsional suspension.
The small movement is generally transmitted and amplified by a spot light and mirror system, but many other systems have also been used.
The electrostatic measuring device can be used for absolute voltage measurements since the calibration can be made in terms of the fundamental quantities of the gap length and forces.
For a constant electrode separation 'd' the integrated forces increase with (Urms)2 and thus the sensitivity of the system for low ranges of the rated voltages of the instrument is small. This disadvantage is
overcome, however by varying the gap length in appropriate steps.
The high pressure gas or even high vacuum between the electrodes provide very high resistivity, therefore the low active power loss.
The measurement of voltages lower than about 50V is , however not possible as the forces become too small.
The load inductance and the electrode system capacitance, however, form a series resonant circuit which must be damped, thus limiting the frequency range.
Sectional view of a 1000 kV standard electrostatic voltmeter using SF6 gas is shown below in Fig. 32.2
A five section capacitor and oil insulated bushing is used to bring the extremely high voltage into the instrument metal tank, filled with pressurized SF6
The HV electrode and earthed plane provide uniform electric fields in the region of the 5 cm diameter disc set in a 65 cm diameter guard plane.
The measurement accuracy of this instrument is of the order of 0.1%.
Principle of Potential Dividers :For the measurement of High Voltages of any type, the best technique is by dividing the voltage. The HV potential divider arms could be pure capacitive, pure resistive or a combination of the two. The essential requirement is that the wave shape to be measured is correctly reproduced on the oscillograph with a known voltage reduction ratio. The general potential divider technique is shown in the following Figure 33.1.
Z1 - the high voltage arm of the divider. It could be pure C, pure R or combination of R and C as per requirement.
Values of Z1 and Z2 are chosen such that the potential across Z2 is around 100 V
The voltage division ratio can be given as; For the circuit in Fig 33.1 where Z"2 = terminal impedence of oscilloscope
For the measurement of high test voltages the technique of potential dividers is most accurate. It provides a continuous measurement of all the types of applied high voltages i.e. dc, ac and impulse. However, the suitability of the type of divider depends upon not only the type of voltage but also upon the range of magnitude of the voltage to be measured.
The types of potential dividers or basically the construction of the HV arm and their suitability are described in the following:
1. Pure Capacitance Voltage Dividers:
The HV arm of the capacitive voltage dividers, usually having their capacitance in pF range, are compressed gas or vacuum capacitors. The nF range HV capacitors are built in stack or in series a number of capacitors made out of polypropylene or paper filled with oil. In the absence of stray capacitances to earth with such HV capacitors, these provide desired exact value of low capacitance and small dimensions of the HV capacitive arm. The value of low voltage arm of the divider is normally chosen in μF range. Compressed gas (SF6) filled HV capacitors are built even above 1000 kV (rms) rating. These can also be used as standard capacitors. In Fig 33.2, a photograph and a sketch of such a capacitor are shown. The value of inductance of the long lead (in mts) connecting the low voltage electrode inside such a capacitor causes problems in giving a good response of the divider. Necessary constructional precautions are therefore taken in their design.
Pure capacitance voltage dividers are suitable for the measurement of power frequency and impulse high voltages. However, the cost of the HV capacitors is high and their cost and size increases with their voltage rating.
2. Pure Resistance Potential Dividers
The high potential drop across a resistive arm by simple Ohm's law is used to reduce the voltage to a measurable quantities, circuits for such measurement are shown in Fig 33.3 (a) and (b)
Such pure resistive arm or divider can be used for the measurement of dc, ac as well as impulse voltages. The wave forms of ac and impulse voltages could also be recorded with the help of an oscilloscope. However, while measuring very high voltages, the resistive arm inductance and stray capacitance cause large error in the accuracy of measurement and hence in response of the measuring device.
The wire-wound resistors used earlier were made of constantan, Cu & Ni, manganin, cu, Mn, Ni or Gr and also of nichrome. To overcome the error caused due to inductance of the wire wound resistors, thin film resistors are now used. A conducting element thin film is deposited on the surface of a glass or ceramic rod or tube. The value of the desired resistance is obtained by varying the thickness of the thin film. Such films could be of carbon, metal oxide; stannic and antimony oxides. Nickel-Chromium thin film is obtained by their evaporation in vacuum. Resistive voltage dividers are produced both
screened (also known as shielded) and unscreened. Since the effect of stray capacitance is not uniform, it causes a non-uniform potential gradient along its length.
3. Mixed Resistive and Capacitive Dividers
The problem caused by the stray capacitance in resistive voltage divider is over come by placing actual capacitors in parallel with the resistor units of the HV arm. This gives rise to a mixed resistive and capacitive divider used for highest voltage range of impulse voltage measurement. These are also known as 'damped capacitive divider' or RC divider. These were first introduced by Elsner in 1939, [6.1 ] . The simplified equivalent circuit of such a divider is shown in Fig 33.4
In this Figure R' represents the resistance of single element of the HV arm where a number of them are in series. C'p represents the capacitance across each of such element and C'e, is the stray capacitance to earth of the element.
References:
1. http://nptel.ac.in/courses/Webcourse-contents/IIT-KANPUR/HighVoltageEngg/ui/Course_home6_30.htm
2. http://www.springer.com/cda/content/document/cda_downloaddocument/9783642453519-c2.pdf?SGWID=0-0-45-1443916-p176426054 3. Arrillaga, Jos; High Voltage Direct Current Transmission, second edition, Institution of Electrical Engineers, ISBN 0 85296 941 4, 1998. 4. Narain G. Hingorani in IEEE Spectrum magazine, 1996. 5. ABB HVDC website. 6. ABB HVDC website. 7. Jos Arrillaga; Yonghe H. Liu; Neville R. Watson; Nicholas J. Murray (9 October 2009). Self-Commutating Converters for High Power Applications. John Wiley and Sons. ISBN 978-0-470-74682-0. Retrieved 9 April 2011. 8. Donald Beaty et al, "Standard Handbook for Electrical Engineers 11th Ed.", McGraw Hill, 1978 9. ACW's Insulator Info – Book Reference Info – History of Electrical Systems and Cables 10. R. M. Black The History of Electric Wires and Cables, Peter Perigrinus, London 1983 ISBN 0-86341-001-4 pages 94–96 11. Alfred Still, Overhead Electric Power Transmission, McGraw Hill, 1913 page 145, available from the Internet Archive 12. "Shaping the Tools of Competitive Power" 13. Thomas P. Hughes, Networks of Power 14. Rissik, H., Mercury-Arc Current Converters, Pitman. 1941, chapter IX.